Make the best use of Scientific Research and information from our 700+ peer reviewed, Open Access Journals that operates with the help of 50,000+ Editorial Board Members and esteemed reviewers and 1000+ Scientific associations in Medical, Clinical, Pharmaceutical, Engineering, Technology and Management Fields.
Meet Inspiring Speakers and Experts at our 3000+ Global Conferenceseries Events with over 600+ Conferences, 1200+ Symposiums and 1200+ Workshops on
Medical, Pharma, Engineering, Science, Technology and Business

A Review about Vector Group Connections In Transformers

Geno Peter .P*

Department of Electrical and Electronics Engineering, Loyola Institute of Technology and Science, Loyola Nagar, Thovalai, Tamilnadu-629302, India

Corresponding Author:
Geno Peter .P
Department of Electrical and Electronics Engineering
Loyola Institute of Technology and Science
Loyola Nagar, Thovalai, Tamilnadu-629302, India

Visit for more related articles at International Journal of Advancements in Technology

Abstract

Transformer is the most important unit in an electrical distribution network. All transformers are subjected to various tests at the manufacturer‟s test laboratory before despatch to the destination of erection. Measurement of turn‟s ratio is one of the routine tests which each transformer has to undergo. In the case of an ordinary winding resistance meter, we can measure the winding resistance and the contact resistance together. It is not possible to measure the contact resistance separately by this meter. Now contact resistance meter is available, it is designed to measure the contact resistances of various Test Objects such as Transformers, Circuit Breakers, Isolators, Bus-bar joints, Welded joints etc. Advanced winding resistance ohmmeter with Dynamic resistance measurement for OLTC is available now with an International trademark. The dynamic resistance measurement detects carbonized spots and weak contacts in the mechanism of a tap changer. In this paper, I wish to discuss the practical differences created in the turn ratio measurement because of the tap switch contact resistance.

Keywords

Transformer, circuit breakers, contact resistance, tap changer

Introduction

The three distinct ways by which a three phase windings can be connected are Star connection, Delta connection and Inter-star connection. Delta and star connections are most commonly used. Inter-star connection finds occasional applications, mostly in specialized constructions like earthing transformer and transformers for multiple pulse circuits. As an example, in a two winding transformer, the primary winding can be connected either in star, or in delta or in inter-star; similarly, the secondary winding can be cOlli1ected in star or in delta or in inter-star. It is common practice to denote high voltage connections in delta by D, in star connection by Y and in inter-star connection by Z. The lower Case letters are applicable for the lower voltage connections (d, y and z). Based on this, it is theoretically possible to connect any pair of windings in a 3 phase transformer in the following pairs of combinations: Dd, Dy, Dz, Yd, Yy, Yz, Zd, Zyand Zz; of this, the first six, are the most commonly encountered ones in practice. As is well known, there is a phase angle difference between primary and secondary voltages. This phase difference varies in steps of 30 degrees (the movement achieved in terms of degrees on a clock when you move from one specified hour position to next). Hence 12'0 clock position represents zero degrees. As we move clockwise, each subsequent hour position adds 30 degrees to the previous position. As examples

➢ l'0 clock position signifies 30 degrees (phase shift of 30 degrees to right)

➢6'0 clock position signifies 180 degrees

➢ 11'0 clock position corresponds to 330 degrees (phase shift of 30 degrees to left)

Depending upon the individual connections, this phase shift (from 0 to 330 degrees in steps of 30 degrees) needs to be mentioned along with connection combination. This is practically done using the corresponding clock position. The clock position indicates the angle by which secondary vector leads or lags the primary vector. In case of Dyn11, the secondary vector leads the primary vector by 30 degrees, where as in Dy1 connection, secondary vector lags the primary vector by 30 degrees

What is polarity?

When the pairs of coils have the same winding direction, then the voltages of induction in both the coils are in the same direction, from one end to the other. But when the two coils are having opposite winding directions, the voltages of induction are in opposite directions. We are applying an alternating voltage to the equipment. Hence there is nothing like a positive or negative polarity. But for connections, we need to consider the instantaneous direction of voltages (polarity) of the selected ends. This basically depends on the directions of the windings and the ends selected for connection. The direction of winding for the coils and the method of interconnection are specified by design department. Winding directions change depending upon the direction of rotation of machine, the direction of copper feeding and the starting (and finishing) ends. It can also change because of manufacturing inconveniences. The verification of polarity for interconnections and of turns ratio is carried out by means of a single phase fed ratiometer . The polarity has to be verified immediately after assembly of coils on the core with top yoke in position, prior to starting any connection activities.

Instantaneous Polarity

The ratiometer establishes the instantaneous polarities of the pairs of windings on a particular limb. It is also necessary that the coil sets on each of the three limbs of a given transformer are all identical in their winding directions.

Let us mark the two windings of high voltage winding as H1 and H2 (it does not matter which one is which). Similarly, let us mark the two ends of low voltage winding as L1 and L2. To establish relative polarities between two windings on a give phase, connect one end of high voltage winding (say H2) to one end of low voltage winding (say L2) on this phase. Apply 230 volts to H1-H2. For this example let us take a ratio of turns to 1. This means that the transformed voltage on LV side is also 230 volts. Measure the voltage between H1 and Ll. One of the two following scenarios can arise either additive or subtractive polarity.

Additive Polarity

As shown in Fig 1., the voltage is 460 volts. This means that, in the voltmeter circuit, the two voltages are, additive. Alternately, the voltage in winding is in direction H2 to H1 and in low voltage winding it is from L1 to L2. This means that the points we have interconnected are not of same polarity. At the give instant, these voltages add. Hence corresponding-terminals of like polarity are H2 and L1 (or H1 and L2)

advancements-technology-additive

Figure 1: Additive Polarity

Subtractive Polarity

As shown in Fig 2., the voltage is zero. This means that in the voltmeter circuit, the two voltages are subtractive. Alternately, the voltage in winding is in direction H2 to H1 and in low voltage winding it is from L2 to L1. This means that the points we have interconnected are of same polarity· At the given instant these voltages subtract. Hence corresponding terminals of like polarity are H1 and L1 (or H2 and L2).

advancements-technology-subtractive

Figure 2: Subtractive Polarity

Verification of Vector group

The ratiometer does precisely this by establishing the correct polarities for the two windings. Once we get the correct ratio with right polarity, then the terminals to which plus terminal of ratiometer HV side and LV side are connected are the like terminals of same polarity for any interconnection. Similarly, the terminals to which the minus terminal of ratiometer HV side and LV side are connected are the like terminals of same polarity (but opposite to that of the first pair) for any interconnection. It is very important to understand the above concept. Once this is clear, the rest is very easy. As an example, assume the three HV terminals to be U, V and W. Let the corresponding LV terminals be u, v, w and n. Then for vector connection Dyn 11, the following is the correspondence between HV and LV side.

advancements-technology-ratiometer

Figure 3: Ratiometer

➢ 'UV' should correspond to 'un'(with U and u being of one polarity; V and n form the second pair of terminals with opposite polarity).

Similarly, 'VW' corresponds to 'vn' and 'WU' corresponds to 'wn'.

Both the following ratiometer connections are correct for vector connection Dyn11, except that whatever mode of connection is chosen, it must be cyclically repeated for all three phases.

Table 1: Ratiometer connections

Conditions for Vector Check

The vector connection forms one of the most important parameters from user's perspective, Hence it is very essential to verify that the inter-winding connections are indeed as per customers' requirements. The ratio meter used for measuring no-load voltage ratio, functions only when primary and secondary winding polarities are identical for the connection made. Hence establishment of the polarity of individual windings is a comparatively easy task. For multi-winding transformers, two definite reference points are physically connected so that it is suitable to apply a 3 phase voltage .A low magnitude (normally about 400 volts) 3 phase AC voltage is applied on the high voltage winding and all the possible voltages are measured.

Example:

We consider the case of a Dyn 11 transformer.

The polarity references phase by phase are:

UV - un ; VW - vn ; WU - wn.

We connect "U" phase of high voltage winding to "u"phase of low voltage winding. We apply - 400 volts, 3 phase voltage at 50 Hz (our supply frequency) to the high voltage delta side. We measure the all possible voltages.

advancements-technology-connections

Figure 4: Vector Group Connections

For connection Dyn 11 ,the following conditions must be satisfied:

Vv=Vw

Wv>Ww

Un + Vn = UV

Wn > Vn

Such a superposition is possible for all types of connections. A voltmeter with a high input impedance has to be used for such measurements (Eg., digital meters)

Winding Directions

The standards define various vector connections. They assume same winding direction in both the windings and indicate corresponding pairs of terminals that gives the required vector group.

Same Winding Directions

The hypothetical helix is in the same direction in both the coils viewed from either end. Hence induced voltages in the energised coil and the other coil are in the same direction; In other words, the terminals 1 and 1 have the same polarity; the terminals 2 and 2 have the same polarity, but the polarity is opposite to that of the pair 1 and 1.

advancements-technology-winding

Figure 5: Same Winding Direction

Opposite Winding Directions

The hypothetical helix has opposite directions in the coils viewed from either end. Hence induced voltages in the energised coil and the other coil are in opposite direction; In other words, the terminals 1 and 1 have opposite polarity; similarly the terminals 2 and 2 have opposite polarity. In transformers with foil winding, the neutral is formed with the outside bus-bars from foil winding. Hence, it is the L V side neutral that should be fixed in all measurements, since based on the sequence of connections, this cannot change.

advancements-technology-opposite

Figure 6: Opposite Winding Direction

Procedure for Interconnection

➢ Establish the polarities using the above method.

➢ Interchange polarity based on required connection (so that neutral in foil connected transformers has the required polarity).

➢ Refer the guidelines given in the Standards for interconnection.

Conclusions

The instantaneous polarity is something we assign. We can assign either positive or negative polarity for a given pair of terminals. The other pair of terminals automatically has the opposite polarity to this pair. The verification of polarity for interconnections and of turns ratio is carried out by means o a single phase ratiometer .Its seen when the windings is of same direction or subtractive polarity the vector group connections are perfect. Theoretically, very low DC voltage pulse can be used for establishing polarity. But in practice, in view of severe effects of inductance in windings and residual magnetism in core, this is never used for transformers. This method is resorted to only for current transformers. This paper did evolve with my practical and theoretical experiences gained during my days in Transformer manufacturing, MNC companies

Acknowledgement

The author wishes to thank Dr.M.Rajaram, Vice-Chancellor, Anna University of Technology, Tirunelveli and Dr. M.T Nicholas, Principal, LITES for their support and encouragement.

References

[1] IEC 60076 -1 , “Power Transformers” –Part 1: General, 2000
[2] IEC 60060-1 , “High Voltage Test Techiques” –Part 1: General, 1989
[3] IEEE/ANSI Standards C57.123“ IEEE Guide for Transformer Loss Measurement“, 2002
[4] ABB , “Testing of Power Transformers“,Zurich,2003
[5] IJOAT ‚ “A review about Testing of Distribution Transformers” ,Vol 2, No 1. Geno Peter. P ,2011

Select your language of interest to view the total content in your interested language
Post your comment

Share This Article

Relevant Topics

Recommended Conferences

Article Usage

  • Total views: 12033
  • [From(publication date):
    April-2011 - Jun 22, 2018]
  • Breakdown by view type
  • HTML page views : 8240
  • PDF downloads : 3793
 

Post your comment

captcha   Reload  Can't read the image? click here to refresh

Peer Reviewed Journals
 
Make the best use of Scientific Research and information from our 700 + peer reviewed, Open Access Journals
International Conferences 2018-19
 
Meet Inspiring Speakers and Experts at our 3000+ Global Annual Meetings

Contact Us

Agri & Aquaculture Journals

Dr. Krish

[email protected]

+1-702-714-7001Extn: 9040

Biochemistry Journals

Datta A

[email protected]

1-702-714-7001Extn: 9037

Business & Management Journals

Ronald

[email protected]

1-702-714-7001Extn: 9042

Chemistry Journals

Gabriel Shaw

[email protected]

1-702-714-7001Extn: 9040

Clinical Journals

Datta A

[email protected]

1-702-714-7001Extn: 9037

Engineering Journals

James Franklin

[email protected]

1-702-714-7001Extn: 9042

Food & Nutrition Journals

Katie Wilson

[email protected]

1-702-714-7001Extn: 9042

General Science

Andrea Jason

[email protected]

1-702-714-7001Extn: 9043

Genetics & Molecular Biology Journals

Anna Melissa

[email protected]

1-702-714-7001Extn: 9006

Immunology & Microbiology Journals

David Gorantl

[email protected]

1-702-714-7001Extn: 9014

Materials Science Journals

Rachle Green

[email protected]

1-702-714-7001Extn: 9039

Nursing & Health Care Journals

Stephanie Skinner

[email protected]

1-702-714-7001Extn: 9039

Medical Journals

Nimmi Anna

[email protected]

1-702-714-7001Extn: 9038

Neuroscience & Psychology Journals

Nathan T

[email protected]

1-702-714-7001Extn: 9041

Pharmaceutical Sciences Journals

Ann Jose

[email protected]

1-702-714-7001Extn: 9007

Social & Political Science Journals

Steve Harry

[email protected]

1-702-714-7001Extn: 9042

 
© 2008- 2018 OMICS International - Open Access Publisher. Best viewed in Mozilla Firefox | Google Chrome | Above IE 7.0 version
Leave Your Message 24x7