alexa Analysis of Water Quality in Urban Water Supply System of Bangladesh

ISSN: 2161-0525

Journal of Environmental & Analytical Toxicology

  • Research Article   
  • J Environ Anal Toxicol 2017, Vol 7(4): 492
  • DOI: 10.4172/2161-0525.1000492

Analysis of Water Quality in Urban Water Supply System of Bangladesh

Tapos Kormoker*, Ram Proshad and Mohammad Mahmud Khan
Patuakhali Science and Technology University, Bangladesh
*Corresponding Author: Tapos Kormoker, Patuakhali Science and Technology University, Bangladesh, Tel: +8801759368602, Email: [email protected]

Received Date: Jul 10, 2017 / Accepted Date: Jul 15, 2017 / Published Date: Jul 20, 2017

Abstract

Supply of safe drinking-water is world-wide considered to be an important issue for public health safety and must be the key objective of water supply systems. The aim of this research is to analyze the supply water quality in urban water supply system of Bangladesh. This research was conducted in two Pourashava water supply systems namely Barguna Pourashava and Faridpur Pourashava of Bangladesh. Some concerned chemical, biological and physical parameters were tested for an initial assessment of the water quality of the source water. A total of ten ground water based production well's water samples were examined in those two Pourashava. A total of nine samples, one from each ward were collected form the entry point of the supply water to the user's house were analyzed for E. coli which represented the quality of the piped water. A total of three water samples were collected from each of the ward for microbiological (FC) quality analysis. Millipore microbiological field testing kits was used for E. coli testing, DR 2800 HACH spectrophotometer was used for determination of manganese, iron, and nitrate and Wegtech Digital Arsenator was used for arsenic determination. Physical parameters were tested by HACH potable instruments. The light brown yellowish color created an aesthetic problem among the water users of Barguna Pourashava. In addition, the fecal contamination rate was very high. The findings of E. coli analysis of Barguna Pourashava supply water indicated that 11% have intermediate risk, 37% have high risk and 52% have very high risk considering the health. The water of the production wells of Faridpur Pourashava has high concentration of the arsenic, iron and E. coli. The household's storage water sample analysis result indicated that 48%, 44% and 7% have very high risk, high risk and intermediate risk from the health point of view.

Keywords: Water quality; Water supply system; Health risks; Contamination; Monitoring; Management; Bangladesh

Introduction

Water supply and sanitation is characterized by a number of achievements and challenges. Urban water supply system has become a more critical issue in the socio-economic condition of a country. It is very important factor now a days and also it indicates the quality of urban life. Bangladesh is one of the most densely populated country in the world. The country has a population density of 1,115.62 people per square kilometer, (2,889.45/square mile), which ranks 10th in the world. Urban people faced a problem of safe drinking water due to lack of appropriate urban water supply system in Bangladesh. The extent and availability of safe drinking water is an important indicator of sustainable development, and access to clean water constitutes a principal components of the Millennium Development Goals (MDGs). There was an estimation that more than 70 percent of the urban population in the developing countries are either have an inadequate water supply or being supplied with unsafe water or both [1]. Safe water and improved sanitation are powerful determinants of health. The WHO program in Bangladesh aims at promoting preventive approaches to water quality management using Water Safety Plans (WSP) to enable utilities, small communities and the households to ensure safety of drinking water. Since the quality of drinking water is closely associated with human health, providing safe drinking water is one of the most important public health priorities. An estimated 80 percent of all diseases and one third of deaths in developing countries are caused by the consumption of contaminated water [2]. About 25 percent of the total population lives in urban Bangladesh, and only 44 percent of the urban people are served with tap water supply [3]. The lower income group is the worst sufferers as because they cannot afford to have safe drinking water for an active and healthy life [4,5]. Present study focus on the water quality analysis in the urban water supply system in Bangladesh with health risk assessment of urban people.

Materials and Methods

Two Pourashava water supply systems were selected considering the geography namely Faridpur Pourashava of Faridpur District (as flood prone area) and Barguna Pourashava of Barguna District (as coastal area) for conducting this research (Figure 1). The Faridpur Pourashava water supply system has around 7600 users and the Barguna Pourashava have 3800 users. The user list was collected from each of the Pourashava which were proportionally distributed in each ward. Some concerned chemical, biological and physical parameters were tested for an initial assessment of the water quality of the source water. Only one ground water based production well's water was examined at Barguna Pourashava and total of nine production well’s water were examined at Faridpur Pourashava. A total of nine samples, one from each ward were collected form the entry point of the supply water to the user's house were analyzed for E. coli which represented the quality of the piped water. A total of three water samples were collected from each of the ward for microbiological (FC) quality analysis. The water samples were collected from the nearest water users of the distribution line in any ward, middle and the farthest. A few household's samples were checked for arsenic. The source water was checked for FC, arsenic, iron, manganese occasionally nitrate. Millipore microbiological field testing kits was used for E. coli testing, DR 2800 HACH spectrophotometer was used for determination of manganese, iron, and nitrate and Wegtech Digital Arsenator was used for arsenic determination. Some physical parameters were also tested namely pH, turbidity, total dissolved solids, conductivity etc. Physical parameters were tested by HACH potable instruments. All the testing was conducted in the field. The water quality testing was conducted by the skilled professionals (Table 1).

environmental-analytical-toxicology-Faridpur-Barguna-Pourashava

Figure 2: Map showing the sampling sites of Faridpur and Barguna Pourashava of Bangladesh.

Water quality parameters Units Bangladesh standards WHO guideline values
Odor   Odorless Odorless
pH   6.0-8.5 6.0-8.5
Electrical conductivity µs/cm 500 500
Turbidity NTU 5.0 5.0
Arsenic mg/l 0.05 0.01
Fe mg/l 0.3 0.3
Mn mg/l 150-600* 250
Nitrate mg/l 40-50 50
E. coli /100ml Absent Absent

Table 1: Water quality parameters and standard [5].

Results and Discussion

Water quality in Barguna Pourashava water supply system

Only one ground water based production well's water was examined for some concerned chemical, biological and physical parameters as presented in Table 2 for an initial assessment of the water quality of the source water. The light brown yellowish color created an aesthetic problem among the water users and the fecal contamination was too high.

No Particulars Unit Results
1 Location   Tulatoli Pump House
2 Source Type   Deep Tube Well
3 Catchment Area/Depth ft 940
4 Color   Light Yellowish Brown
5 Odor   Smell of Rotten Egg
6 pH   8.16
7 ORP mV -155.8
8 Electrical conductivity µs/cm 1158
9 Salinity mg/l  
10 LOD mg/l 2.83
11 Turbidity NTU 1.1
12 As mg/l 0
13 Fe mg/l 0.05
14 Mn mg/l 0.4
15 Nitrate mg/l 8.5
16 E. coli /100ml TNTC
17 Other coli form /100ml TNTC
18 Total coli form /100ml TNTC

TNTC: To numerous to count) in the source water

Table 2: Water quality analysis result of production wells of Barguna Pourashava water supply system.

A total of nine samples, one from each ward were collected form the entry point of the supply water to the user's house were analyzed for E. coli which represented the quality of the piped water. The analysis results are presented in Table 3. The result indicated that the supply line water in one wards has intermediate risk of microbiological contamination considering the health and the remaining have variable degrees of risk. Three household's storage samples were collected randomly from each of the 9 wards of the Pourashava for microbiological analysis and the total samples collected samples were 27. The analysis results were categorized by considering the E. coli concentration per 100 ml; namely 0 for low risk, 1-10 medium risk, and 11-99 high risk and above 100 is very high risk. The analysis result indicated that 11% have intermediate risk, 37% have high risk and 52% have very high risk of considering the health (Table 4).

Ward No Microbial Risk (HH's source water sample)
Low Intermediate High Very High Grand Total
Ward 1     1   1
Ward 2       1 1
Ward 3       1 1
Ward 4     1   1
Ward 5   1     1
Ward 6     1   1
Ward 7       1 1
Ward 8       1 1
Ward 9     1   1
Grand Total 0 1 4 4 9

Table 3: Microbiological analysis of the household's source water samples of Barguna Pourashava.

Ward No Microbial Risk (% of household’s storage water sample)
Intermediate High Very High Grand Total
Ward 1 33 (1) 67 (2)   100 (3)
Ward 2 33 (1)   67 (2) 100 (3)
Ward 3   33 (1) 67 (2) 100 (3)
Ward 4     100 (3) 100 (3)
Ward 5 33 (1)   67 (2) 100 (3)
Ward 6   67 (2) 33 (1) 100 (3)
Ward 7   67 (2) 33 (1) 100 (3)
Ward 8   33 (1) 67 (2) 100 (3)
Ward 9   67 (2) 33 (1) 100 (3)
Grand Total 11 (3) 37 (10) 52 (14) 100 (27)

( ) indicated number of sample

Table 4: Microbiological analysis of the household's storage water samples of Barguna Pourashava.

Water quality in Faridpur Pourashava water supply system

The analysis results of water samples collected from nine production well of the Faridpur Pourashava water supply system is presented in Table 5. The result indicated for high concentration of the arsenic, iron and E. coli in the production well's water. A total of nine samples, one from each ward were collected form the entry point of the supply water to the user's house were analyzed for E. coli which represented the quality of the piped water. The analysis results are presented in Table 6. The result indicated that the supply line water in two wards has low risk of microbiological contamination considering the health and the remaining have variable degrees of risk. The Table 7 represents the analysis result of E. coli of the household's storage water sample. The result indicated that 48%, 44% and 7% have very high risk, high risk and intermediate risk from the health point of view.

No Particulars Unit Goal Chamot 1 Goal Chamot 2 Goal Chamot 3 Goal Chamot 4 Jhiltuli 1 Jhiltuli 2 Jhiltuli 3 Jhiltuli 4 Jhiltuli 5
1 Location   In front gate Salim's house Bishorgon Ghat Bus stand Road side Moshiur's house Anis's house Behind filter house Mizan's house
2 Source Type   STW STW STW STW STW STW STW STW STW
3 Depth   380 300 290 300 290 290 295 290 300
4 Color   Reddish Reddish Reddish Reddish Light Reddish Light Reddish Light Reddish Light Reddish Light Reddish
5 Odor   Fishy Smell Fishy Smell Fishy Smell Fishy Smell Fishy Smell Fishy Smell Fishy Smell Fishy Smell Fishy Smell
6 pH   7.50 7.09 7.42 7.18 7.24 7.44 7.34 7.26 7.16
7 ORP mV 150.1 155.4 148.4 168.7 53.9 102.3 20.6 58.8 22.4
8 Conductivity µs/cm 1462 1693 1040 1091 1035 1019 852 894 440
9 Salinity mg/l                  
10 LOD mg/l 6.99 7.28 6.85 7.47 4.24 4.77 3.07 4.74 7.56
11 Turbidity NTU 57.6 64.3 82.4 136.0 69.6 67.0 81.5 69.2 58.8
12 As mg/l 170 235 225 135          
13 Fe mg/l 6.8 8.9 14.6 11.6 6.3 4.1 3.2 2.6 2.45
14 Mn mg/l 0.4 0.3 0.3 0.9 0 0 0.3 0.3 0.4
15 Nitrate mg/l 0 0 0 0 0 0 0 0 0
16 E. coli /100ml 30 25 31 TNTC 36 112 12 54 53
17 Other coli form /100ml 280 37 192 TNTC 80 204 35 43 47
18 Total coli form /100ml 310 62 223 TNTC 116 316 47 97 100

TNTC: To numerous to count) in the source water

Table 5: Water quality analysis result of the production tube wells of Faridpur.

Ward No Microbial Risk (HH's source water sample)
Low Intermediate High Very High Grand Total
Ward 1   1     1
Ward 2     1   1
Ward 3   1     1
Ward 4   1     1
Ward 5 1       1
Ward 6 1       1
Ward 7     1   1
Ward 8       1 1
Ward 9     1   1
Grand Total 2 3 3 1 9

Table 6: Microbiological analysis of the household's source water samples of Faridpur Pourashava.

Ward No Source Microbial Risk (HH's storage water sample)
Low Intermediate High Very High Grand Total
Ward 1 Intermediate     100 (3)   100 (3)
Ward 2 High   33 (1) 67 (2)   100 (3)
Ward 3 Intermediate     33 (1) 67 (2) 100 (3)
Ward 4 Intermediate     67 (2) 33 (1) 100 (3)
Ward 5 Low     67 (2) 33 (1) 100 (3)
Ward 6 Low   33 (1)   67 (2) 100 (3)
Ward 7 High       100 (3) 100 (3)
Ward 8 Very High       100 (3) 100 (3)
Ward 9 High     67 (2) 33 (1) 100 (3)
Grand Total     7 (2) 44 (12) 48 (13) 100 (27)

(_) indicated number of samples

Table 7: Microbiological analysis of the household's storage water samples of Faridpur Pourashava.

Conclusion

Urban water supply system in Bangladesh is not satisfactory because it possess human health risk. It is a threat to urban people as they suffer from different diseases due to drink these contaminated supply water in Bangladesh. There observe in both Barguna and Faridpur Pourashava that E. coli have a great negative impact on human health of Bangladeshi people. It causes very high health risk to urban people. Government should take necessary steps for reducing the risk of supply water contamination.

Acknowledgements

This works was supported by the Department of Public Health Engineering Bangladesh. Their help is sincerely acknowledged.

References

Citation: Kormoker T, Proshad R, Khan MM (2017) Analysis of Water Quality in Urban Water Supply System of Bangladesh. J Environ Anal Toxicol 7: 492. Doi: 10.4172/2161-0525.1000492

Copyright: © 2017 Kormoker T, et al. This is an open-access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.

Select your language of interest to view the total content in your interested language

Post Your Comment Citation
Share This Article
Relevant Topics
Recommended Conferences
Article Usage
  • Total views: 753
  • [From(publication date): 0-2017 - Jul 16, 2018]
  • Breakdown by view type
  • HTML page views: 626
  • PDF downloads: 127

Post your comment

captcha   Reload  Can't read the image? click here to refresh
Leave Your Message 24x7