Make the best use of Scientific Research and information from our 700+ peer reviewed, Open Access Journals that operates with the help of 50,000+ Editorial Board Members and esteemed reviewers and 1000+ Scientific associations in Medical, Clinical, Pharmaceutical, Engineering, Technology and Management Fields.
Meet Inspiring Speakers and Experts at our 3000+ Global Conferenceseries Events with over 600+ Conferences, 1200+ Symposiums and 1200+ Workshops on
Medical, Pharma, Engineering, Science, Technology and Business

Simulation of a Vacuum Cooling System for the Phosphoric Slurry: “ Flash Cooler ”

Abdennebi N1* and Hajji N2
1National School of Engineers of Gabes (ENIG), University of Gabes, University City, Gabes, Tunisia
2Laboratory of Energy and Environment, ENIG, University City, Gabes, Tunisia
Corresponding Author : Abdennebi N
National School of Engineers of Gabes (ENIG)
University of Gabes, University City, 6029, Gabes, Tunisia
E-mail: [email protected]
Received February 18, 2013; Accepted May 27, 2013; Published May 30, 2013
Citation: Abdennebi N, Hajji N (2013) Simulation of a Vacuum Cooling System for the Phosphoric Slurry: “Flash Cooler”. J Chem Eng Process Technol 4:159. doi:10.4172/2157-7048.1000159
Copyright: © 2013 Abdennebi N, et al. This is an open-access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.
Related article at
DownloadPubmed DownloadScholar Google

Visit for more related articles at Journal of Chemical Engineering & Process Technology

Abstract

The present study concerns the phosphoric slurry cooling using a vacuum system “flash cooler”. This system has a dual purpose, the first is to ensure the desired cooling of the phosphoric slurry and the second and the mainly purpose is to reduce the fluorine content in the exhaust gas outlet of the phosphate attack units. A simulation was made through the Aspen Plus software features of this vacuum system which is composed of a flash cooler to cool the slurry, a spray tower to clean the fluorinated gas and recovered it to a fluosilicic acid solution and a barometric condenser to create the vacuum all over the system. The determination of the different operating parameters of each device in order to minimize the amount of fluorine released into the atmosphere and maximizes his recovery as a solution of fluosilicic acid, were investigated. The obtained results confirmed the good performance of this system and showed that it is possible to cool the slurry to the desired phosphoric slurry temperature and get a good discount rate of fluorine released into the atmosphere. This pollutant is recovered as fluosilicic acid solution to 20% by mass.

Keywords
Fluorine removal; Flash cooler; Absorption; Fluosilicic acid; Simulation
Introduction
Emissions from the phosphoric acid process in the Chemical Tunisian Group include fluorides gaseous as hydrogen fluoride (HF) and silicon tetra fluoride (SiF4). The gases are released during the attack on the phosphate rock. These gases, if they are released into the atmosphere unchecked, can have a negative impact on the environment. The reduction of these pollutants is in absorption towers operated under vacuum. In these towers, fluorinated gases are absorbed and recovered into a solution of fluosilicic acid at 20% by mass. This solution can be neutralized or it can serve as feedstock for the production of aluminum fluorine, hydrofluoric acid and cryolite later. Note that the temperature of gas outlet from the phosphoric unit is at 70°C, the maximum rates allowed fluoride in the effluent is determined by the Tunisian standard norm to 10 mg/Nm3[1].
Vacuum system reducing fluorine content
The system used for cooling the phosphoric slurry and for reducing the amount of fluoride released during the phosphate attack is shown in Figure 1.
This system includes a “flash cooler” which is the mainly equipment to cool the phosphorus slurry. A pump is installed at the exit of the flash to recycle the cooled slurry in the attack tank. The steam derived from the flash cooler full of fluoride is washed in a column using a spray solution of fluosilicic acid as an absorption solution. The purpose of this column is to absorb the fluoride found as a form of HF and SiF4 and recovered it into a fluosilicic acid solution at 20% by mass. The washed gas derived from the spray tower then passes into a barometric condenser which is responsible for creating the vacuum in all the system adopting a sea water drop.
Process simulation
The main objective of the process simulation is to find the optimal operating conditions:
• To maximize the recovery of fluorine,
• To ensure cooling of 3-4 degrees Celsius of the slurry at most,
• To obtain a solution of fluosilicic acid at 15-20 wt%.
To simulate this vacuum system, we used the software features over Aspen Plus. The different models of unit operations used are presented in Table 1, while interconnections between these different models are shown in the block diagram (Figure 2).
Note that the unit system used is the ‘’METCBAR’’ which expresses the temperature in °C, the pressure in bar and the mass flow in kg/h.
Operating parameters of the vacuum system
The simulation was made on the basis of an estimated composition of the phosphoric slurry [2,3]. The different parameters of the system to get the desired aims are listed in Table 2. The flash and the barometric condenser are assumed adiabatic.
The principles reactions considered in this system are:
H+ + F- ↔ HF (1)
SiO2 + 6 F- + 2 H2O ↔ SiF6 -- + 4 OH- (2)
SiO2 + 4 HF ↔ SiF4 + 2 H2O (3)
Results and Interpretation
It was found that the three degrees of cooling of the phosphoric slurry is provided by a pressure of 240 mmHg at the flash. The simulation results showed that the pressure in the flash cooler has a much influence on the composition of the gas leaving it. Note that the rate of HF in the gas leaving decreases with the pressure of the flash while the rate of SiF4 increases (Figure 3 and Figure 4). Figure 5 shows the effect of barometric condenser pressure on the consumption of sea water that provides a total condensation. It is clear that a greater flow of sea water is necessary to achieve a higher vacuum.
In addition, Table 3 recapitulate the different results obtained after this simulation. We can conclude that this vacuum system has almost eliminate the fluorine rate from the gas atmosphoric emission and recovered it as a fluoscilicic acid solution 20% by mass. It’s clear that also the condensed gas released at the sea water contain some traces of fluorine, which confirm a good performance of this system.
Conclusion
In this work, we have elaborated a simulation of a vacuum cooling system of phosphoric slurry by the functionality of Aspen Plus features. This system comported a flash cooler, a spray tower responsible for the absorption of fluorine, a barometric condenser for reaching the vacuum on the whole of the system. This simulation has approved that we can assure the three degrees of cooling by a pressure of 0, 32 bars in the flash and offers a good abatement of fluorine which is recovered into a fluosilicic acid solution at 20 % by mass.
References



Tables and Figures at a glance

image   image   image
Table 1   Table 2   Table 3

 

Figures at a glance

image   image   image   image   image
Figure 1   Figure 2   Figure 3   Figure 4   Figure 5
Select your language of interest to view the total content in your interested language
Post your comment

Share This Article

Recommended Conferences

  • World Bioenergy Congress and Expo
    July 02-04, 2018 Berlin, Germany
  •  International Conferenceand Expo on Oil and Gas
    August 09-10, 2018 Madrid, Spain
  • International Conference on Chemical Engineering
    September 17-18, 2018 Vancouver, Canada

Article Usage

  • Total views: 12423
  • [From(publication date):
    August-2013 - Apr 21, 2018]
  • Breakdown by view type
  • HTML page views : 8582
  • PDF downloads : 3841
 

Post your comment

captcha   Reload  Can't read the image? click here to refresh

Peer Reviewed Journals
 
Make the best use of Scientific Research and information from our 700 + peer reviewed, Open Access Journals
International Conferences 2018-19
 
Meet Inspiring Speakers and Experts at our 3000+ Global Annual Meetings

Contact Us

Agri & Aquaculture Journals

Dr. Krish

[email protected]

1-702-714-7001Extn: 9040

Biochemistry Journals

Datta A

[email protected]

1-702-714-7001Extn: 9037

Business & Management Journals

Ronald

[email protected]

1-702-714-7001Extn: 9042

Chemistry Journals

Gabriel Shaw

[email protected]

1-702-714-7001Extn: 9040

Clinical Journals

Datta A

[email protected]

1-702-714-7001Extn: 9037

Engineering Journals

James Franklin

[email protected]

1-702-714-7001Extn: 9042

Food & Nutrition Journals

Katie Wilson

[email protected]

1-702-714-7001Extn: 9042

General Science

Andrea Jason

[email protected]

1-702-714-7001Extn: 9043

Genetics & Molecular Biology Journals

Anna Melissa

[email protected]

1-702-714-7001Extn: 9006

Immunology & Microbiology Journals

David Gorantl

[email protected]

1-702-714-7001Extn: 9014

Materials Science Journals

Rachle Green

[email protected]

1-702-714-7001Extn: 9039

Nursing & Health Care Journals

Stephanie Skinner

[email protected]

1-702-714-7001Extn: 9039

Medical Journals

Nimmi Anna

[email protected]

1-702-714-7001Extn: 9038

Neuroscience & Psychology Journals

Nathan T

[email protected]

1-702-714-7001Extn: 9041

Pharmaceutical Sciences Journals

Ann Jose

[email protected]

1-702-714-7001Extn: 9007

Social & Political Science Journals

Steve Harry

[email protected]

1-702-714-7001Extn: 9042

 
© 2008- 2018 OMICS International - Open Access Publisher. Best viewed in Mozilla Firefox | Google Chrome | Above IE 7.0 version